05




























 
Building decontamination and accompanying analytical procedures
Up until the 1970s, creosote was used in buildings, one of its purposes being to provide protection against damp. Nowadays it is known that creosote releases carcinogenic and odour-intensive substances, yet many contaminated buildings are still in use today. This article will present an example of successful decontamination in which accompanying air analysis and analysis of the various building materials proved indispensable.
In the year 2000, the Swiss Agency for the Environment, Forests and Landscape (BUWAL) issued a warning concerning the presence of carcinogenic substances in creosoted railway sleepers. The sleepers had been soaked in creosote which contains highly odorous and carcinogenic substances. Analyses conducted by the Swiss testing institute Empa have revealed that even after 25 years two-thirds of the creosote still remains in the sleepers and is constantly evaporating or leaching out. Up until the 1970s, creosote was also used in buildings as a means of protecting floors from damp, and as a timber protection agent. Mouldy and unpleasant odours often bear witness to the application of such applications. Experience in the field of chemical indoor air analysis shows that the air concentrations of these harmful substances remain unchanged over decades, meaning that there can be no reduction in the concentration unless decontamination measures are undertaken, i.e. unless the source is removed.

Experience still lacking
In many cases, the carcinogenic effect of creosote and the odour pollution it causes result in the decision to undertake decontamination. Unlike with asbestos and PCB, where decontamination procedures are well established and have passed the test of time, there is still little experience available in the area of cleaning up buildings contaminated with creosote and disposing of contaminated building materials. For one thing, the high toxicity of the substances and the risk that ceilings and floors could become contaminated when building waste containing creosote is removed demand increased protective measures to be taken with respect to both the building and personnel. Air analyses can be performed to assess which protective measures are necessary. For another thing, the high proportion of odorous substances and the special way that building waste contaminated by creosote reacts to fire means that particular requirements have to be met as regards disposal, ruling out normal waste disposal or incineration in waste incineration plants or cement factories. One argument against landfill dumping is the large proportion of highly water-soluble compounds, while incineration in cement plants is not an option due to the high proportion of odorous substances, and incineration in conventional waste incineration plants is not possible on account of the material's viscosity.

Difficult to achieve one hundred percent decontamination The first priority when dealing with odourintensive substances is to remove their source. Even the tiniest residues of harmful substances can endanger the success of the decontamination process. As we have seen from the example of the railway sleepers, creosote is still able to release harmful substances into the ambient air even after many years and a constant air flow. The complete removal of the harmful substances in practice, however, especially in the case of creosote, poses major problems. In many places, creosote was spilt on the ground, and as a result has seeped over the years into concrete and walls to a depth of up to 20 centimetres.
Often the building's supporting elements were contaminated, meaning that a complete removal of the source is virtually impossible and consideration has to be given to sealing measures. There are a number of products available on the market for sealing buildings against harmful substances, but not all meet the practical requirements of the building industry. Besides providing a reliable seal against the odorous substances, they need above all to be easy to apply and guarantee leak tightness even on pipes, wires, sills etc. In this case, better results are achieved by means of casting than with composite films lined with aluminium. It is very difficult to seal pipe connections using composite films, yet many casting processes have not been tested with respect to their contaminant retention capacity, meaning that only limited statements can be made about the longterm success of such methods.

Analytical methods to accompany decontamination Objective evaluation data are needed to ensure that the correct measures are initiated in decontamination projects, which can frequently prove very expensive. One reliable and sensitive method of analysing volatile organic components is gas chromatography with mass selective detection. Thermal desorption technique is used to collect samples. This method can be used to analyse both air and material samples, and has been established for some years now at Dräger's Analytical Services laboratory. The advantages of the low detection limits and wide substance spectrum, encompassing a wide boiling range (especially high-boiling components like naphthalene compounds), are of great significance, particularly in this application example.

Thermal desorption tubes (filled with Tenax TA) are used for air sampling on site. These are reusable sampling tubes which are stored in air-tight containers rather than being sealed by melting.

The sampling process can be done using pumps such as the Dräger Accuro or Quantimeter. A sampling volume of just three to five litres is sufficient to be able to reliably detect naphthalene concentrations right down to the lower μg/m3 range. At the same time, short sampling times are also possible. The chromatogram shows clearly the significant proportion of naphthalene compounds as a percentage of the total contamination of a room.
From the results of the air analysis, it is clear which rooms are contaminated. To find out which materials may be possible contaminant sources in these rooms, samples were taken from suspicious building materials. In the laboratory of Dräger Analytical Services, direct thermal desorption was used to analyse the various material samples. This method involves thermally desorbing the weighed out material at an increased temperature and transfering the desorbed substances to the GC system. The emitted substances are focused in a cold trap and then analysed by gas chromatography with a mass selective detector. Even the tiniest sample quantities are sufficient for this method. The contaminant source can be clearly identified on the basis of the chromatograms (as in Figure 2, for example). In this way, the source can be individually removed and any secondary emission sources identified.

Practical testing of casting processes
When a schoolhouse needed to be decontaminated in the city of Zurich, a casting process was applied and the necessary accompanying measurements performed. Generally speaking, the nose is the best way to assess odour intensive substances such as the naphthalene to be found in creosote, as its smell can be perceived even at low concentrations in the microgram range. This is also the case when it comes to locating contaminant sources. Nevertheless, indoor air measurements represent a useful method of objectively and quantitatively assessing the progress of decontamination activities. A person's sense of smell is greatly impaired and distorted when exposed to the sort of high solvent concentrations which typically occur at building sites. In this respect, chemical air analyses show themselves to be a low-cost, robust and reliable alternative. The measurements conducted during the course of the schoolhouse decontamination showed that the casting process was able to significantly reduce the concentrations in the ambient air of the contaminants naphthalene, diphenyl and dibenzofuran contained in the creosote. However, before the main contaminant sources can be removed, the rooms in question have to be stripped back to the bare brickwork. The next step, which involved sealing the floors, reduced the contaminant concentration by somewhat more than half (see Figure 3: bar marked "after decontamination"). The seal was improved in a second step, adapted better to the pipe connections, among other things, and extended to include the base area. This considerably improved the success of decontamination, as the third bar in the graph shows.

Decontamination goal achieved
Since these measures were able to achieve the decontamination goal – that the substances should no longer be present in harmful concentrations nor should their odour be perceptible – the shell of the building was then approved for the construction phases I and II. Once all the decontamination work had been completed, another air analysis was performed. This showed for one thing that the jointless floor, floor coverings and mineral plaster have no additional sealing effect because the contaminant concentration was hardly reduced as construction work continued (see fourth bar in Figure 3). For another thing, the casting method proved to be very good in the short term, i.e. two months after the sealing process. The first leak tightness tests conducted six months after the end of the construction phase also showed positive results (see fifth bar in the graph in Figure 3, marked "6 months after end of construction") and would lead one to assume a good long-term result of the chosen variant.

Conducting air analyses to accompany decontamination measures also showed clearly that extensive decontamination work can fully eliminate the diphenyl and dibenzofuran. In the case in question, the odour intensive naphthalene was reduced by a factor of 10, thus bringing it down to below the odour perception threshold. It was not possible to eliminate it entirely, however, because the remaining contaminants rise up inside the walls and are released by diffusion into the room. A glance at similar decontamination projects in Germany, however, shows that other methods of decontamination are only able to achieve a factor 2 to 5 reduction in the contaminant concentrations.

Quality of construction work is crucial Successful decontamination of odour intensive contaminants can be achieved, in other words, by more or less completely removing the sources and sealing surfaces by means of casting. However, if contaminants have been allowed to spread throughout a building over a longer period of time and have penetrated the walls, complete elimination will prove difficult. By implementing additional improvements and optimizing the seal in critical areas, the contaminant concentrations were reduced again by a factor of three.
This shows that the decontamination of odour intensive substances places the highest possible demands on the quality of the construction work and the choice of materials.

Philipp Thalmann und Reto Coutalides
Beratungen + Messungen AG
www.raumlufthygiene.ch

Dirk Rahn-Marx
Dräger Safety AG & Co. KGaA
www.draeger.com/analysenservice

Back Print e-mail to a colleague
     

Dräger Safety AG & Co. KGaA
Revalstrasse 1
23560 Luebeck, Germany
Tel +49 451 882 0
Fax +49 451 882 2080

Access to local websites

Download the article